• Attachment methods of metal plate electrical wiring covers
Attach the metal plate electrical wiring covers as shown below.
1) Lean the metal plate electrical wiring cover as shown in the figure and attach tab (1) on the lower side to the electrical
wiring box.
2) Attach tab (2) on the lower side of the metal plate electrical wiring cover.
3) Push in the upper part of the metal plate electrical wiring cover and attach the 3 tabs.
CAUTION
Make sure that the shaded part (
) will
not go inside the electrical wiring box.
Refrigerant Piping Work
, install as described in the installation manual supplied with the multi outdoor unit.
1. Flaring the pipe end.
1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing downward
so that the chips do not enter the pipe.
3) Put the flare nut on the pipe.
4) Flare the pipe.
5) Check that the flaring is properly made.
WARNING
1) Do not use mineral oil on flared part.
2) Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
3) Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.
4) Do never install a drier to this R410A unit in order to guarantee its lifetime.
5) The drying material may dissolve and damage the system.
6) Incomplete flaring may cause refrigerant gas leakage.
6
Tab (1)
Tab (1)
Tab (2)
Tab
With a multi indoor unit
(Cut exactly at
right angles.)
Remove burrs
Flaring
Set exactly at the position shown below.
A
Die
A
Flare tool for R410A
Clutch-type
0-0.5mm
Clutch-type (Rigid-type)
1.0-1.5mm
Wing-nut type (Imperial-type)
1.5-2.0mm
Conventional flare tool
Check
Flare’s inner
surface must
be flaw-free.
The pipe end must
be evenly flared in
a perfect circle.
Make sure that the