Troubleshooting
SiBE12-908
147
Service Diagnosis
Troubleshooting
Check No.02
Refer to P.169
P4
: Radiation fin thermistor
J3
: Discharge pipe thermistor
J6
: Outdoor heat exchanger thermistor
J8
: Liquid pipe thermistor
J9
: Gas pipe thermistor
H9
: Outdoor air thermistor
(R9446)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
NO
Check No.02
Thermistor resistance check
Turn on the power supply again
Does the remote
controller display
the error code
again?
NO
NO
YES
Is it OK?
YES
Check No.02
Thermistor resistance check
Is it OK?
YES
Reconnect properly.
Replace the thermistor.
Replace the thermistor.
Replace the outdoor unit
PCB.