Troubleshooting
SiBE12-908
149
Service Diagnosis
Troubleshooting
Check No.02
Refer to P.169
Check No.03
Refer to P.170
Check No.05
Refer to P.170
(R9447)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Turn off the power and turn it on
again.
Does the fault
appear again? Does
the outdoor fan run?
(Note on resetting power supply)
WARNING
To cool down the electricals, the
outdoor unit fan gets started when
the radiation fin temperature rises
above 75°C even when the air
conditioning is not operated and
stops itself when it drops below
70°C.
YES
NO
Check No.02
Thermistor resistance check
To reset the unit, power off status
need to continue at least 30 seconds
Fin thermistor
Check the radiation fin
temperature
Does the thermistor
meet the specification
chart of thermistor?
NO
YES
Does the temperature
exceed the temperature
to stop operation?
NO
YES
Replace the fin thermistor.
Replace the outdoor unit
PCB.
Replace the fan motor.
Rectify the connector and
the fan motor lead wire.
Replace the outdoor unit
PCB.
Outdoor fan system
check
Check No.05
NO
YES
Too dirty
Radiation fin dirty?
Slightly dirty
Check No.03
Installation condition check
Clean up the radiation fin.