SiBE12-908
Troubleshooting
Service Diagnosis
132
2.16 Outdoor Unit PCB Abnormality
Remote
Controller Display
E1
Method of
Malfunction
Detection
Detect within the program of the microcomputer that the program is in good running order.
Detect input of zero-cross signal.
Malfunction
Decision
Conditions
When the program of the microcomputer is in bad running order.
Zero-cross signal can not be detected.
Supposed
Causes
Out of control of microcomputer caused by external factors
z
Noise
z
Momentary fall of voltage
z
Momentary power loss
Defective outdoor unit PCB
Breakage of harness between PCBs
Troubleshooting
(R9437)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Does the LED A
blink?
Power on again
Replace the outdoor unit
PCB.
NO
YES
Check to see that the unit is
grounded.
NO
YES
NO
Grounded?
Is harness in good
order?
YES
Carry out grounding work.
Zero-cross signal is fault.
Replace the outdoor unit
PCB.
Replace harness.