Outdoor Unit
SiBE12-908
233
Removal Procedure
7
Disconnect the
connector for the
overload protector
[S40].
[S40] : Overload protector
8
Disconnect the
connectors [S20],
[S21], and [S80].
[S20] : (white) Electronic
expansion valve coil for
room A
[S21] : (red) Electronic
expansion valve coil for
room B
[S80] : Four way valve coil
9
Disconnect the
connector for the relay
harness of compressor.
10
Disconnect the 2
connectors for the
reactor.
Step
Procedure
Points
(R9942)
[S40]
(R9943)
[S21] [S20]
[S80]
(R9944)
(R9945)