Troubleshooting
SiBE12-908
163
Service Diagnosis
2.36 Heater Wire Abnormality
Remote
Controller Display
PA
Method of
Malfunction
Detection
A fault is identified when the outlet temperature of humidifying fan does not reach a certain
temperature within a given time after the heater turned on.
Malfunction
Decision
Conditions
When the temperature detected by the thermistor is lower than the outdoor temperature (at
heater turned off) + 5°C, and this condition continues for 30 minutes.
Supposed
Causes
Breakage of heater filament
Breakage of heater harness
Abnormal temperature detected by outdoor temperature thermistor
Abnormal temperature detected by humidification fan outlet thermistor
Damaged main relay
Blown thermal fuse
Damaged heater control part
Extremely low voltage