SiBE12-908
Check
Service Diagnosis
178
If NG in step 2
→
Defective PCB
→
Replace the PCB.
If NG in step 4
→
Defective Hall IC
→
Replace the outdoor fan motor.
If OK in both steps 2 and 4
→
Replace the PCB.
<For hygroscopic fan motor>
Check that the connectors HK1, HK2, HK3 for proper connection.
1. Check that the power supply voltage is applied between HK1 and HK3.
2. If NG in step 1
→
Defective PCB
→
Replace the PCB.
When the FU2 is melted, check the rotor motor for proper function.
FU1
SW power supply
Hygroscopic fan motor
FU2
Outdoor fan motor
Humidifying fan motor
Four way valve