SiBE12-908
Main Functions
Function and Control
24
Time chart for
humidifying
operation control
Approx. 1 minute after HUMID HEAT operation start up, it repeats humidifying and drying
alternately (to protect condensation for inside the hose).
Time chart for HUMID HEAT operation on trial mode
HUMID HEAT operation on trial mode works in the same sequence as HUMID HEAT
operation, but about 30 minutes later it automatically stops.
Remark
When a room is spacious such as loft style or partitioned by accordion style curtain, the
ventilation volume is large and may not sometimes reach the set humidity.
. Humidifying time
Approx. 70min.
Decide time according to the outdoor temperature
and hose length set by remote controller.
. Drying time
Approx. 2~10min.
Decide time according to the hose length set by
remote controller.
’. Drying time
Approx. 2~10min.
'
'
(R9412)
HUMID HEAT
operation
Humidifying fan
and damper
Hygroscopic
fan
Heater
Rotor
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Dry mode
Approx. 1min
15 sec.
15 sec.
Approx. 3min