Troubleshooting
SiBE12-908
135
Service Diagnosis
2.19 DC Fan Lock
Remote
Controller Display
E7
Method of
Malfunction
Detection
Identify the fan motor system fault based on fan speed detected by Hall IC during high pressure
fan motor running.
Malfunction
Decision
Conditions
When the fan motor is running, the fan does not rotate for 150 seconds or more.
Shut down when the error repeats 16 times
Clear condition: The fan continuously rotates for 11 minutes. (without fault)
Supposed
Causes
Failure in fan motor
Disconnection or improper connection of harness/connector between fan motor and PCB
The fan does not rotate because it gets caught in foreign matter
Troubleshooting
Check No.23
Refer to P.177
(R9440)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Try to operate
NO
YES
Check the outdoor unit PCB for
rpm command pulse input
Check No. 23
Is the connector of
the fan motor
disconnected?
NO
YES
Is the pulse input?
YES
NO
Is there any foreign
matter around the
fan?
Turn off the power supply,
then insert the connector.
Remove them.
Replace the outdoor fan
motor.
Replace the outdoor unit
PCB.