SiBE12-908
Troubleshooting
Service Diagnosis
166
Troubleshooting
(R9457)
[ ]
Check No.02
Refer to P.169
Check No.05
Refer to P.170
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is it OK?
Check connector for proper
connection
NO
Reconnect properly.
YES
NO
YES
Cool it
down.
Is it OK?
Is the heater cooled
well after the power
supply turned off?
YES
NO
NO
At normal temperature:
44.6
Ω
±10%
NO
YES
Check No.02
Is the resistance of
humidification thermistor
within normal range?
Replace the thermistor.
Replace the heater ASSY.
*The humidification
thermistor is exclusive for
fan outlet temperature.
YES
NO
YES
NO
YES
NO
YES
YES
NO
Check No.02
Thermistor resistance check
Measure resistance between
heater connectors
Is the heater resistance
appropriate?
Turn on the power supply again and
run the unit in HUMID HEAT test
operation mode.
Does the humidifying rotor
motor run?
Does the air blow
out from the
hygroscopic fan?
Does the air blow
out from the
humidifying fan?
Is there foreign material?*
Check No.05
Outdoor fan
system check
Replace the thermistor.
Replace the humidifying
rotor motor.
*At HUMID HEAT mode
instead of test mode, the
ON timing of the
hygroscopic fan may delay
20 min. at maximum.
To "
P9
" troubleshooting
Remove foreign material.
Replace the outdoor unit
PCB.
*Include inside the humidification
hose and indoor air supply filter.