Troubleshooting
SiBE12-908
141
Service Diagnosis
2.23 Compressor Sensor System Abnormality
Remote
Controller Display
H0
Method of
Malfunction
Detection
Fault condition is identified by DC current which is detected before compressor startup.
Malfunction
Decision
Conditions
When the DC voltage is 50 V or less.
Supposed
Causes
Defective PCB
Harness disconnection / defective connection
Troubleshooting
Replace the outdoor unit PCB.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.