Troubleshooting
SiBE12-908
167
Service Diagnosis
2.38 Lights-out of Microcomputer Status Lamp
Remote
Controller Display
—
Method of
Malfunction
Detection
When a microcomputer fault is detected, LED A turns off.
Malfunction
Decision
Conditions
Supposed
Causes
Outdoor unit PCB is not power supplied
Power supply failure due to noise
Troubleshooting
(R9458)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is correct power supplied?
Is LED A turned off?
Is voltage of 5 V
applied b5V
and GND ?
Restart
Does the LED A blink?
*For the unit with standby power
save function, first set the ON
timer using remote controller to
release the standby power save
function.
NO
YES
Turn on power supply.
Turn on breaker.
NO
YES
YES
YES
*Do not work on or touch
components other than
specified part. (Doing so
may cause a short circuit.)
Replace outdoor unit PCB.
Replace outdoor unit PCB.
Replace outdoor unit PCB.
Remove noises (from the
power supply).
NO