InteliDrive DCU Marine - 3.0.0 Global Guide
135
Setpoint group
Engine protect
Related FW
3.0.0
Range [units]
0 .. 60 [s]
Default value
20
Step
1
Comm object
10024
Related applications
All
Config level
Standard
Setpoint visibility
Always
Description
This parameter adjusts delay after engine start when alarms configured as RunOnlyBlkDel2 (i.e. "running
only", group #2) are started to be evaluated. The "running only" alarms are not beeing evaluated while the
engine is not running or then, after start, while the adjusted delay is running.
For details see drawing, which is part of
description.
RunOnlyBlkDel2