InteliDrive DCU Marine - 3.0.0 Global Guide
174
Protections
Protection group contains all Analog inputs and Binary inputs protection limits and delays. List is dynamically
created during configuration process.
8.1.3 Binary Inputs
Any InteliDrive controller extension physical binary input can be configured as “function” or “protection”.
Following chapter contains Logical binary inputs list that can be configured to any physical input.
ID-DCU MARINE binary inputs
Remote Start, Remote Stop, Rem Start/Stop
are not active in LOC (local)
mode.
Note:
Minimal input pulse duration is 120 ms to be detected as valid (binary inputs sampling rate is 100 ms).
Adjustable delay can be configured to any binary input when is used as a protection: Standard = 0,5 sec or one
of BinInp delay 1, 2, 3 that can be adjusted by corresponding Setpoint BinInp Delay 1, 2, 3.
Input
BI delay configuration
Setpoint
Standard (0,5s)
BinInp delay 1
BinInp Delay 1
BinInp delay 2
BinInp Delay 2
BinInp delay 3
BinInp Delay 3
See setpoints BinInp delay 1 [s] etc…