InteliDrive DCU Marine - 3.0.0 Global Guide
124
Setpoint group
Engine params
Related FW
3.0.0
Range [units]
0,0 .. 10,0 [Bar]
Default value
10,0
Step
0,1
Comm object
9681
Related applications
All
Config level
Standard
Setpoint visibility
Always
Description
Oil pressure limit when controller stops cranking = one of the engine running indications.
To activate this function any Analog input must be configured to Analog logical input Oil press.
Note:
Step, Range and dimension depend on corresponding Analog input sensor characteristic.
Starting POil
Setpoint group
Engine params
Related FW
3.0.0
Range [units]
0,0 .. 10,0 [Bar]
Default value
10,0
Step
0,1
Comm object
10138
Related applications
PRP
Config level
Standard
Setpoint visibility
Always
Description
Coolant pressure limit = one of the engine running indications. To activate this function any Analog input
must be configured to Analog logical input Coolant press.
Note:
PRP only
Note:
Step, Range and dimension depend on corresponding Analog input sensor characteristic.
StartPCoolant
Summary of Contents for InteliDrive DCU Marine
Page 29: ...InteliDrive DCU Marine 3 0 0 Global Guide 29 Protection delay and blocking ...
Page 51: ...InteliDrive DCU Marine 3 0 0 Global Guide 51 4 2 2 Electronic engine without redundancy line ...
Page 255: ...InteliDrive DCU Marine 3 0 0 Global Guide 255 Analog inputs from J1939 configuration ...
Page 265: ...InteliDrive DCU Marine 3 0 0 Global Guide 265 Engine Values ...
Page 285: ...InteliDrive DCU Marine 3 0 0 Global Guide 285 6 back to Appendix 6 back to Table of contents ...