InteliDrive DCU Marine - 3.0.0 Global Guide
125
Setpoint group
Engine params
Related FW
3.0.0
Range [units]
0 .. 600 [s]
Default value
2
Step
1
Comm object
8394
Related applications
All
Config level
Standard
Setpoint visibility
Always
Description
Time the binary output Prestart is active prior to engine start (Start request sending to ECU). Set to zero if
you want to start immediately after Start button is pressed (the Prestart output stays opened). RPM must be
zero during
Prestart time
otherwise the Starting procedure is not activated.
Prestart Time
Setpoint group
Engine params
Related FW
3.0.0
Range [units]
1 .. 200 [s]
Default value
8
Step
1
Comm object
8234
Related applications
All
Config level
Standard
Setpoint visibility
Always
Description
Amount of time the controller will crank the engine in an attempt to start.
MaxCrank Time
Setpoint group
Engine params
Related FW
3.0.0
Range [units]
CMB, EME: 3 ..200 [s], AUX, PRP: 0 .. 200 [-]
Default value
8
Step
1
Comm object
8257
Related applications
All
Config level
Standard
Setpoint visibility
Always
Description
Pause between cranking attempts.
CrankFailPause
Summary of Contents for InteliDrive DCU Marine
Page 29: ...InteliDrive DCU Marine 3 0 0 Global Guide 29 Protection delay and blocking ...
Page 51: ...InteliDrive DCU Marine 3 0 0 Global Guide 51 4 2 2 Electronic engine without redundancy line ...
Page 255: ...InteliDrive DCU Marine 3 0 0 Global Guide 255 Analog inputs from J1939 configuration ...
Page 265: ...InteliDrive DCU Marine 3 0 0 Global Guide 265 Engine Values ...
Page 285: ...InteliDrive DCU Marine 3 0 0 Global Guide 285 6 back to Appendix 6 back to Table of contents ...