InteliDrive DCU Marine - 3.0.0 Global Guide
79
5 Controller setup
5.1 PLC - programmable functions
Following programmable functions are available in ID-DCU MARINE-3.0.0 software.
Use DriveConfig-3.3 or higher software to configure PLC functions.
5.1.1 General specification
Each function output can be configured to:
another function input
any physical terminal (e.g. to controller’s physical Binary Output) - DriveConfig I/O sheet
Each function limit (parameter) can be configured as:
constant limit (fix): just write requested value into the field (-32768 to +32767)
setpoint limit (customer adjustable): click on field and select one from PLC setpoint list
any value (e.g. from Analog input): click on field and select one from controller or PLC values list
All PLC function analog inputs are signed type and that is why the following analog values must not be
configured to any comparator and PID analog input:
Load Sharing: ThrottlePos.
Info: ECU DiagSource, Timer val, PasswordDecode.
Statistics: NumSuccStarts, NumUnscStarts, Service time.
All function limits and analog outputs must follow input analog value format:
e.g. input value is 0,0 to 10,0 bars, then setpoint limit is e.g. 3,2.
Any time and delay limit is in 0,1s step in the range 0,1 to 3276,7 sec.
PLC consistency check indicates incorrect PLC configuration.
Binary
List contains 128 internal binary values (bits)
PLC Bout 1.1 to PLC BOUT 16.8
that
can be configured as any PLC function binary input or output.
Only used
PLC Bout x.x
can be configured to ID-DCU MARINE controller or external
modules physical terminals.
Used values are visible at controller screen.
Analog
There are available 96 internal analog values
PLC Aout 1
to
PLC Aout 96
that can be
configured as any PLC function input or output.
Any used
PLC Aout x
can be configured as physical analog output.Used values are
visible at controller screen.
PLC resource
Unsigned value that is automatically used for
Counter
and
Timer
functions, 16 PLC
resources are available.
Values are visible in InteliMonitor only.
PLC values
Summary of Contents for InteliDrive DCU Marine
Page 29: ...InteliDrive DCU Marine 3 0 0 Global Guide 29 Protection delay and blocking ...
Page 51: ...InteliDrive DCU Marine 3 0 0 Global Guide 51 4 2 2 Electronic engine without redundancy line ...
Page 255: ...InteliDrive DCU Marine 3 0 0 Global Guide 255 Analog inputs from J1939 configuration ...
Page 265: ...InteliDrive DCU Marine 3 0 0 Global Guide 265 Engine Values ...
Page 285: ...InteliDrive DCU Marine 3 0 0 Global Guide 285 6 back to Appendix 6 back to Table of contents ...