InteliDrive DCU Marine - 3.0.0 Global Guide
100
7 Technical data
7.1 ID-DCU MARINE
Nominal power supply
24 VDC
Power supply range
8 – 36 VDC
Current consumption (depends on supply
voltage)
0.34 A at 8 VDC
0.12 A at 24 VDC
0.09 A at 36 VDC
Galvanically isolated from controller body
YES
Battery voltage measurement tolerance
2 % at 24 V
RTC battery life-cycle
10 year
Power supply
Note:
RTC battery flat causes wrong Date&Time information only.
Operating temperature ID-DCU MARINE
-20 to +70 °C
Operating temperature ID-DCU-LT
-40 to +70 °C
Storage temperature
-30 to +80 °C
Humidity
95 % without condensation
Flash memory data retention time
10 years
Protection front panel
IP65
Standard conformity
Low Voltage Directive
EN 61010-1:95 +A1:97
Electromagnetic Compatibility
EN 61000-6-2, October 2001
EN 61000-6-4, October 2001
IEC 60533, Ed. 2; 1999-11
Vibration
5 – 25 Hz, ±1.6mm
25 – 100 Hz, a = 4 g
Shocks
a = 200 m/s2
Heat radiation
9 W
Operating conditions
Dimensions
(183×123×47 mm)
See chapter terminals and dimensions
Weight
800 g
Dimensions and weight
Summary of Contents for InteliDrive DCU Marine
Page 29: ...InteliDrive DCU Marine 3 0 0 Global Guide 29 Protection delay and blocking ...
Page 51: ...InteliDrive DCU Marine 3 0 0 Global Guide 51 4 2 2 Electronic engine without redundancy line ...
Page 255: ...InteliDrive DCU Marine 3 0 0 Global Guide 255 Analog inputs from J1939 configuration ...
Page 265: ...InteliDrive DCU Marine 3 0 0 Global Guide 265 Engine Values ...
Page 285: ...InteliDrive DCU Marine 3 0 0 Global Guide 285 6 back to Appendix 6 back to Table of contents ...