InteliDrive DCU Marine - 3.0.0 Global Guide
22
Note:
It is possible to download the Actual InteliDrive controller object description corresponding to actual
configuration from on-line controller or from aid archive using DriveConfig software.
Detail Modbus command description see in ComAp Communication guide.
2.2.6 Password protection
Password is a four-digit number. Only setpoints associated with the entered password level can be modified.
There are three levels of password protection.
0
- User level allows change of non-protected setpoints only
1
- Operator level allows change of setpoints protected by Operator level 1.
2
- Master level allows change of setpoints protected by Operator 1. and Master level 2.
3
- Supervisor highest level allows all setpoints or configuration changes, firmware upgrade.
There can be password protected:
Setpoints (depends on configuration)
Statistics values (Level 3 only)
Engine commands (depends on configuration)
Even though one level may have been set from the front panel, the affected setpoints are not accessible from
InteliMonitor (direct or Modem) until this level is set in InteliMonitor (direct or Modem). Setpoints opened from
front panel are automatically closed 15 minutes after the last key has been depressed or when wrong value of
password is set.
Any password can be changed once that level password or higher has been entered if the change is made
from InteliMonitor PC tool.
Password level 3 must be entered at first to change any password if the change is made by controller front
panel buttons.
Note:
"Engine Cmd" Password protection blocks Engine commands: Start, Fault reset, Horn reset from front panel
ID-DCU MARINE, by InteliMonitor, Modbus, ID-DCU-MARINE, InteliVision 5 CAN (Backlit), InteliVision 8
Marine or SMS.
"Engine Cmd" Password protection does not block: activation via Binary inputs.
The following three options protect against modification of statistics values from InteliMonitor.
There is no other access to modify statistics - i.e. can not be changed from panel.
Clear statistics is common protection for all three statistic values.
Setting of statistic is possible protect separately - from Monitor only
2.2.7 WebSupervisor
WebSupervisor is web based system designed for monitoring and controlling ComAp controllers via the
Internet. This system offers a number of beneficial features that help optimize revenue for machinery fleets, as
each piece of equipment can be individually monitored for all important operation values.
ID-DCU Marine connection into WebSupervisor
Connection of ID-DCU Marine controllers can be realized in two different ways:
1. Internet connection via AirGate - using InternetBridge-NT (IB-NT). No fixed and public IP address is needed.
2. Internet connection without AirGate - using InternetBridge-NT (IB-NT) or IG-IB module. The module has to
have fixed and public IP address.
Summary of Contents for InteliDrive DCU Marine
Page 29: ...InteliDrive DCU Marine 3 0 0 Global Guide 29 Protection delay and blocking ...
Page 51: ...InteliDrive DCU Marine 3 0 0 Global Guide 51 4 2 2 Electronic engine without redundancy line ...
Page 255: ...InteliDrive DCU Marine 3 0 0 Global Guide 255 Analog inputs from J1939 configuration ...
Page 265: ...InteliDrive DCU Marine 3 0 0 Global Guide 265 Engine Values ...
Page 285: ...InteliDrive DCU Marine 3 0 0 Global Guide 285 6 back to Appendix 6 back to Table of contents ...