InteliDrive DCU Marine - 3.0.0 Global Guide
189
Related FW
3.0.0
Related applications
All
Comm object
167
Description
This input changes state of logical binary output
Droop Sw
that can be configured as J1939 output to
change ECU mode. Input is active only when
Basic setting
: Governor Mode = BIN.INPUT (DROOP when
closed).
BI Droop
Related FW
3.0.0
Related applications
All
Comm object
168
Description
This input changes state of logical binary output Second RPM Sw that can be configured as J1939 output to
change ECU mode. Input is active only when Basic setting: Speed Select = BIN.INPUT.
BI Second RPM
Related FW
3.0.0
Related applications
All
Comm object
169
Description
This input changes state of logical binary output
Idle/Nominal
that can be configured as J1939 output to
change ECU mode. Input is active only when
Basic setting
: Idle/Nominal = BIN.INPUT.
BI Idle
Related FW
3.0.0
Related applications
All
Comm object
172
Description
Rem Start/Stop is level signal that activates engine start when closed and stop after is opened. It is inactive
in LOC (Local) mode.
It is not possible to stop engine by panel Stop button and by Binary input Remote Stop when Rem Start/Stop
is active. Rem Start/Stop input can be configured to Binary output Timer active to enable engine automatic
start/stop function – see Basic settings / Timer setpoints.
Note:
Engine “Start fail” is Warning (level 1) protection and does not block another start when Rem
Start/Stop is still closed. To prevent unlimited number of starts – configure on LBO Start fail Sd
protection.
Note:
Engine stays running when Rem Start/Stop is opened in controller LOC (Local) mode.
Rem Start/Stop
Summary of Contents for InteliDrive DCU Marine
Page 29: ...InteliDrive DCU Marine 3 0 0 Global Guide 29 Protection delay and blocking ...
Page 51: ...InteliDrive DCU Marine 3 0 0 Global Guide 51 4 2 2 Electronic engine without redundancy line ...
Page 255: ...InteliDrive DCU Marine 3 0 0 Global Guide 255 Analog inputs from J1939 configuration ...
Page 265: ...InteliDrive DCU Marine 3 0 0 Global Guide 265 Engine Values ...
Page 285: ...InteliDrive DCU Marine 3 0 0 Global Guide 285 6 back to Appendix 6 back to Table of contents ...