InteliDrive DCU Marine - 3.0.0 Global Guide
131
Setpoint group
Engine params
Related FW
3.0.0
Range [units]
[DIESEL, GAS]
Default value
DIESEL
Step
[-]
Comm object
9100
Related applications
All
Config level
Standard
Setpoint visibility
Always
Description
Selection of
FUEL SOLENOID
output function.
DIESEL:
The output is still closed except the Engine Params: Stop Time timer if stop command is sent to an
engine.
GAS:
Ignition is activated (binary output Ignition is closed) when RPM is over the 30 RPM (fix value). Gas
valve (binary output Gas is closed) is opened 1 sec after Ignition output.Gas output opens after stop
command or in pause between repeated start.
If the gas engine is unsuccessful in starting the starter output will stay energized 25% longer in order to vent
the remaining gas.
Example of FUEL SOLENOID output behavior during unsuccessful start.
Fuel Solenoid