Parameter
Parameter manual
b maXX
®
1000
Document no. 5.07004.03
59
4
P0863
is not equal to 0.0,
= 0 to 2, and there is no communication on the
bus during the time out detection period, „cE10“ will be shown on the keypad.
P0864
P0865
This parameter is the response delay time after b maXX
®
1000 receives communication
command as shown in the following. 1 unit = 2 ms.
Figure 15:
Response delay time
P0863
RS485Time-out Erkennung
0.0 to 120.0 s
EE
RS485Time-out detection
0.0 s
ON
BM_u_RS485TimeOutDetect
10:1
-
Value
Meaning
0.0
Disable
0.1 to 120.0 s
Time-out detection enabled
P0864
RS485Kommunikationsprotokoll
0 to 5
EE
RS485 Communication protocol
3
STOP
BM_u_RS485CommProtocol
1:1
-
Value
Meaning
0
7, N, 2 (Modbus, ASCII)
1
7, E, 1 (Modbus, ASCII)
2
7, O, 1 (Modbus, ASCII)
3
8, N, 2 (Modbus, RTU)
4
8, E, 1 (Modbus, RTU)
5
8, O, 1 (Modbus, RTU)
P0865
RS485 Antwortverzögerungszeit
0 to 200
EE
RS485 Response delay time
1 [2 ms]
ON
BM_u_RS485ResponseDelayTime
1:1
-