Parameter description
Parameter manual
b maXX
®
1000
Document no. 5.07004.03
Baumüller Nürnberg GmbH
48
4.3
P0805
This parameter determines the response of the drive upon power on and operation com-
mand source is changed.
When the operation command source is from external terminal and operation command
is ON (FWD/REV DCM=closed), the b maXX
®
1000 will operate according to
after power is applied.
P0805
Anlaufsperre
0 to 3
EE
Line start lockout
1
STOP
BM_u_LineStartLockout
1:1
-
Value
Meaning
0
Disable. Operation status is not changed even if operation command source
changed.
1
Enable. Operation status is not changed even if operation command source
changed.
2
Disable. Operation status will change if operation command source
is changed.
3
Enable. Operation status will change if operation command source
is changed.
Start lockout (Run when power is ON)
Operation status when operation command
source is changed
0
Disable (b maXX
®
1000 will run)
Keep previous status
1
Enable (b maXX
®
1000 doesn’t run)
Keep previous status
2
Disable (b maXX
®
1000 will run)
Change according to the new operation command
source
3
Enable (b maXX
®
1000 doesn’t run)
Change according to the new operation command
source