Drive Management
Parameter manual
b maXX
®
1000
Document no. 5.07004.03
15
3
11 OPERATION ENABLED
QUICKSTOP ACTIVE
n
Event:
m
Command ’quickstop’ or
m
Quickstop input = Low (default quickstop input MI5 = 23)
n
Action:
m
Quickstop function is activated
12 QUICKSTOP ACTIVE
INHIBIT START
n
Event:
m
Command ’inhibit voltage’ or
m
Quickstop is stopped (speed 0 has been reached)
m
Pulse enable input MI6 = Low
n
Action:
m
Drive operation is inhibited
13 All conditions
ERROR REACTION ACTIVE
n
Event:
m
Drive error is recognized
n
Action:
m
Error-dependable error reactions are activated
m
Ready-to-operate relay is switched off (multi function relay)
14 ERROR REACTION ACTIVE
ERROR
n
Event:
m
Error reaction is completed
n
Action:
m
Drive operation is inhibited
15 ERROR
INHIBIT READY TO START
n
Event:
m
Command ’reset error’ or
m
RESET ERROR input = Low
→
High (multi function digital input)
n
Condition:
m
Error doesn’t exist anymore
n
Action:
m
Reset error is carried out
16 QUICKSTOP ACTIVE
OPERATION ENABLED
n
Event:
m
Command ’operation enabled’
n
Condition:
m
Quickstop reaction (
) Quickstop reaction ( or is set to
’Remain in quickstop” (values 4 to 7) or
m
Quickstop-input = High (default quickstop input MI5 = 23)
m
Pulse enable input MI6 = High
n
Action:
m
Drive function is enabled again