Parameter
Parameter manual
b maXX
®
1000
Document no. 5.07004.03
53
4
P0814
This parameter is used to select the frequency command at drive stop for keypad and
RS485 communication.
P0815
This parameter sets the initial frequency setpoint for keypad and RS485 communication.
P0816
You can read the master frequency command source by this parameter.
P0814
Auswahl der Frequenzvorgabe
0 to 2
EE
Initial frequency selection
0
STOP
BM_u_InitialFreqSelection
1:1
-
Value
Meaning
0
By current frequency command
1
By zero frequency command
2
By frequency display at
P0815
Anfangsfrequenz Keypad und RS485 Sollwert
0.00 to 600.00 Hz
EE
Keypad and RS485 initial frequency setpoint
60.00
STOP
BM_u_KeypadRS485InitialFrequSet
100:1
-
P0816
Anzeige der Quelle der Masterfrequenzvorgabe
0 to 7
-
Display the master frequency command source
1
A
BM_u_DisplayMasterFrequCommandSource
1:1
-
Display value
Bit
Meaning
1
Bit 0
1: Master frequency command source by first frequency source
(
)
2
Bit 1
1: Master frequency command source by second frequency source
(
)
4
Bit 2
1: Master frequency command source by multi-input function