Parameter description
Parameter manual
b maXX
®
1000
Document no. 5.07004.03
Baumüller Nürnberg GmbH
40
4.3
m
Bit 4: Ramp function generator inhibit
1: enable ramp function generator
0: inhibit ramp function generator (output set to 0)
(a quickstop is executed if ramp function generator status is not STOP)
m
Bit 5: Ramp function generator stop
1: enable ramp function generator
0: inhibit ramp-up/ramp-down ramp function generator
(output frequency is frozen if ramp function generator is in ramp-up or ramp-down
phase)
m
Bit 6: Ramp function generator zero
1: enable ramp function generator
2: ramp function input is set to 0
(set output frequency by ramp to 0)
m
Bit 7: Drive manager command „Quit error“
This command is executed when bit 7 changes from 0
⇒
1.
P0301
This parameter is the output word used in the status machine of the device control.
1)
These bits are low active.
2)
Display operational status of device manager
P0301
Statuswort
0 to 65535
-
Statusword
0
A
BM_u_Status word
1:1
-
Bit
Meaning
0
2)
1: Ready-to-start
0: Not ready-to-start
1
2)
1: Switched on
0: Not ready-to-operate
2
2)
1: Operation enabled
0: Operation inhibited
3
2)
1: Error
0: No error
4
1) 2)
1: Mains voltage DC link voltage is present
0: Mains voltage DC link voltage is not present
5
1) 2)
1: No requirements quickstop
0: Quickstop (or quickstop requirements are available)
6
2)
1: Inhibit
0: No inhibit
7
1: Warning
0: No warning
8
Ramp function generator in status STOP
9
Reserved
10
1: Setpoint reached
0: Setpoint not reached
11
1: Internal limit active (current, speed)
0: No internal limit active
15 ... 12
Reserved