Parameter
Parameter manual
b maXX
®
1000
Document no. 5.07004.03
135
4
P1380
This parameter is used in conjunction with
set 4 to input a set point in Hz.
P1381
This parameter is used to set detection of the offset between set point and feedback.
When the offset is higher than the setting of
for a time exceeding the setting of
, the b maXX
®
1000 will output a signal when
and
is set to
16.
P1382
This parameter defines the time during which the PID feedback must be abnormal before
a warning (see
) is given. It also can be modified according to the system feed-
back signal time.
P1383
When the actual output frequency
≤
and the time exceeds the setting of
, the b maXX
®
1000 will be in sleep mode.
When the actual frequency command >
and the time exceeds the setting of
, the b maXX
®
1000 will restart.
When the b maXX
®
1000 is in sleep mode, frequency command is still calculated by PID.
When frequency reaches wake up frequency, b maXX
®
1000 will accelerate from
minimum frequency following the V/f curve.
P1380
Quelle PID Sollwert
0.00 to 600.00 Hz
EE
Source of PID set point
0.00
ON
BM_u_SourcePIDSetPoint
100:1 Hz
-
P1381
PID Offset
1.0 to 50.0 %
EE
PID offset level
10.0 %
STOP
BM_u_PIDOffsetLevel
10:1
-
P1382
Ansprechzeit PID Offset
0.1 to 300.0 s
EE
Detection time of PID offset level
5.0 s
STOP
BM_u_DetectionTimePIDOffsetLevel
10:1
-
P1383
Ansprechzeit Stand-by
0.0 to 6550.0 s
EE
Sleep/wake up detection time
0.0 s
STOP
BM_u_SleepWakeUpDetectionTime
10:1
-