Parameter
Parameter manual
b maXX
®
1000
Document no. 5.07004.03
29
4
P0077
The motor auto tuning procedure will set this parameter. The user may also set this pa-
rameter without using the auto tuning procedure, see
.
P0110
The rated current of the drive
is regarded as 100 %. The setting of the motor
no-load current will affect the slip compensation.
The setting value must be less than
.
P0111
Refer to the rated rpm and the number of polepairs on the type plate of the motor and use
the following equation to calculate the rated slip:
Rated slip (Hz) = F
Motor nominal frequ.
(
) - (rated rpm
⋅
motor pole pairs
⋅
120)/60
This parameter is valid only in vector mode.
can be calculated via
automatically if unknown.
can be
changed only if
= 0.
P0112
This parameter may be set so that the drive will increase its voltage output to obtain a
higher torque. Only to be used for V/f control mode.
P0077
Motor Ständerwiderstand
0 to 65535 m
Ω
abc
EE
Motor line-to-line resistance
0 m
Ω
abc
STOP
BM_u_MotorStatorResist
1:1
abc
-
P0110
Motor Leerlauf-Strom
0.0 to 99.0 %
EE
Motor no-load current
40.0 %
ON
BM_u_MotorNoLoadCurrent
10:1
-
P0111
Motor Nennschlupf
0.00 to 20.00 Hz
EE
Motor rated slip (Motor nominal slip)
3.00 Hz
STOP
BM_u_MotorRatedSlip
100:1
-
P0112
Drehmomentanpassung
0.0 to 10.0 Hz
EE
Torque compensation
0.0 Hz
ON
BM_u_TorqueComp
10:1
-
NOTE
Too high torque compensation can overheat the motor.