Parameter
Parameter manual
b maXX
®
1000
Document no. 5.07004.03
27
4
P0050
Not implemented.
P0051
Not implemented.
P0053
This parameter determines the maximum output voltage of the drive. The maximum out-
put voltage setting must be smaller than or equal to the rated voltage of the motor as in-
dicated on the motor nameplate. This parameter value must be equal to or greater than
the mid-point voltage
.
The maximum value depends on the b maXX
®
used, up to 255.0 V for single-phase de-
vices and up to 510.0 V for three-phase devices.
P0054
Parameters
and
must be set if the drive is programmed to operate
in vector control mode (
= 1). They also must be set if the „electronic thermal
overload relay“
functions are selected.
Motor current: motor rated current in [A] on the motor.
b maXX
®
1000: rated current of used b maXX
®
P0050
Motor Typenschlüssel
0
hex
to FFFF
hex
EE
Motor type code
-
STOP
BM_u_MotorType
1:1
-
P0051
Motor Seriennummer
0 to 65535
EE
Motor serial number
0
STOP
BM_ud_MotorSerialNr
1:1
-
P0053
Motor Nennspannung
0.1 to 255.0 V or
0.1 to 510.0 V
EE
Motor rated voltage
220.0 V or 440.0 V
STOP
BM_u_MotorNomVolt
10:1 V
-
P0054
Motor Nennstrom
EE
Motor rated current
ON
BM_u_MotorNomCurrent
10:1
-