Parameter
Parameter manual
b maXX
®
1000
Document no. 5.07004.03
89
4
P1110
Assignment of the multi function outputs:
P1110
Multi-Funktions-Ausgang Relais (RA1, RB1, RC1)
0 to 21
EE
Multi function output relay (RA1, RB1, RC1)
8
STOP
BM_u_MultiFunctionOutputRelayRA1
1:1
-
Value
Function
Description
0
No function
1
b maXX® 1000 operational
Active when the b maXX® 1000 is ready or RUN com-
mand is „ON“
2
Master frequency attained
Active when the b maXX® 1000 reaches the output fre-
quency setting.
3
Zero speed
Active when command frequency is lower than the mini-
mum output frequency.
4
Over-torque detection
Active as long as over-torque is detected. (Refer to
)
5
Baseblock (B.B.) indication
Active when the output of the b maXX® 1000 is shut off
during base block. Base block error code 051D
hex
can be
forced by multi-function input (setting 9).
6
Low-voltage indication
Active when low voltage (Lv) is detected
7
Operation mode indication
Active when operation command is controlled by external
terminal.
8
Fault indication
Active when a fault occurs, see error list
9
Desired frequency attained
Active when the desired frequency
is attained.
10
Terminal count value attained
Active when the counter reaches terminal count value
11
Preliminary count value attaint
Active when the counter reaches preliminary count value
12
Over voltage stall supervision
Active when the over voltage stall function operating
13
Over current stall supervision
Active when the over current stall function operating
14
Heat sink overheat warning
When heatsink overheats, it will signal to prevent OH turn
off the b maXX® 1000. When it is higher than 85°C
(185°F), it will be ON.
15
Over voltage supervision
Active when the DC link voltage exceeds level
16
PID supervision
Active when the PID function operating
17
Forward command
Active when the direction command is FWD
18
Reverse command
Active when the direction command is REV
19
Zero speed output signal
Active when the drive is standby or STOP
20
Communication warning (FbE,
Cexx, AoL2, AUE, SAvE)
Active when there is a communication warning, e.g. warn-
ing codes: 00A0
hex
, 050E
hex
, 050F
hex
, 0513
hex
, 0514
hex
,
0525
hex
21
Brake control (desired fre-
quency attained)
Active when output frequency
≥
. Deactivated
when output frequency
after STOP command
22
Inverter ready
Drive is ready.