Parameter description
Parameter manual
b maXX
®
1000
Document no. 5.07004.03
Baumüller Nürnberg GmbH
66
4.3
P0897
When momentary power loss is detected, the b maXX
®
1000 will block its output and then
wait for a specified period of time (determined by
, called base-block time) be-
fore resuming operation. This parameter should be set at a value to ensure that any re-
sidual regeneration voltage from the motor on the output has disappeared before the
drive is activated again.
This parameter also determines the waiting time before resuming operation after external
baseblock and auto restart after fault
.
When using a PG card with PG (encoder), speed search will begin at the actual PG (en-
coder) feedback speed.
P0898
Following a momentary power loss, the b maXX
®
1000 will start its speed search opera-
tion only if the output current is greater than the value set by
. When the output
current is less than the value of
, the b maXX
®
1000 output frequency is at
„speed synchronization point“. The drive will start to accelerate or decelerate back to the
operating frequency at which it was running prior to the power loss.
Figure 19:
Momentary power loss operation
P0897
Basiszeit für Geschwindigkeitssuche (BB)
0.1 to 5.0 s
EE
Baseblock time for speed search (BB)
0.5 s
STOP
BM_u_BaseBlockTimeSpeedSearch
10:1
-
P0898
Stromgrenze für Geschwindigkeitssuche
30 to 200 %
EE
Current limit for speed search
150 %
STOP
BM_u_CurrentLimitForSpeedSearch
1:1
-