Parameter
Parameter manual
b maXX
®
1000
Document no. 5.07004.03
81
4
P1101
This parameter is used to select the terminals to be internal terminal or external terminal.
You can activate internal terminals by
. A terminal cannot be both internal ter-
minal and external terminal at the same time.
For standard b maXX
®
1000 (without extension card), the multi-function input terminals
are MI1 to MI6 as shown in the following.
Figure 25:
Multi function input terminals (internal/external)
The Setting method is convert binary number to decimal number for input.
For example:
If setting MI3, MI5, MI6 to be internal terminals and MI1, MI2, MI4 to be external terminals.
The setting value should be
bit5 x 2
5
+ bit4 x 2
4
+ bit2 x 2
2
= 1 x 2
5
+ 1 x 2
4
+ 1 x 2
2
= 32 + 16 + 4 = 52 as shown in
the following.
Figure 26:
Multi function input terminals (internal/external)
P1101
Interner/externer Multi-Funktions-Eingang Auswahl 0 to 4095
EE
Internal/external multi function input terminals
selection
0
STOP
BM_u_IntExtMultiFunctionInputTerminals
1:1
-