Parameter
Parameter manual
b maXX
®
1000
Document no. 5.07004.03
111
4
P1168
This parameter sets the function of the AO2 output 0 to +10 V
DC
(ACM is signal ground),
see also
P1169
This parameter sets the voltage range of the analog output signal AO2.
is set to 0, the analog output voltage is directly proportional to the output
frequency of the b maXX
®
set to 100 %, the maximum output fre-
quency
of the b maXX
®
1000 corresponds to +10 V
DC
on the AO2 output.
Similarly, if
is set to 1, the analog output voltage is directly proportional to the
output current of the b maXX
®
set to 100%, then 2.5 times the rated
current corresponds to +10 V
DC
on the AO2 output.
For Example: When using the meter with full scale of 5 volts, adjust
to 50 %. If
is set to 0, then 5 V
DC
will correspond to maximum output frequency.
P1168
Analoges Ausgangssignal AO2
0 to 1
EE
Analog output signal AO2
0
STOP
BM_u_AnalogOutputSignal2
1:1
Value
Meaning
0
Analog frequency meter (0 to maximum output frequency)
1
Analog current meter (0 to 250 % of rated current)
P1169
Analoges Ausgangssignal Verstärkung AO2
0 to 200 %
EE
Analog output gain AO2
100 %
STOP
BM_u_AnalogOutputGain AO2
1:1
NOTE
Any type of voltmeter can be used. If the meter reads full scale at a voltage less than 10 V,