Parameter
Parameter manual
b maXX
®
1000
Document no. 5.07004.03
137
4
P1385
This parameter sets the wake up frequency, for further information see
P1386
This is the source selection of minimum output frequency when control is by PID.
Complete PID diagram see
.
P2030
The function of this parameter is to input the password that is set in
. Input the
correct password here to enable changing parameters. You are limited to a maximum of
3 attempts. After 3 consecutive failed attempts, a blinking „error code 0503
hex
„ will show
up to force the user to restart the b maXX
®
1000 in order to try again to input the correct
password.
P1385
PID Stand-by Einschalt-Frequenz
0.00 to 600.00 Hz
EE
PID wake up frequency
0.00
STOP
BM_u_WakeUpFrequency
100:1 Hz
-
P1386
Minimale PID Ausgangsfrequenz mode
0 to 1
EE
Minimum PID output frequency selection
0
STOP
BM_u_PIDFeedbackSignalDetectionTime
1:1
-
Value
Meaning
0
By PID control
1
By minimum output frequency (
P2030
Passwortschutz Eingabe
0 to 9999
EE
Password protect input
0
STOP
BM_u_PasswordProtectInput
1:1
-
Value
Meaning
0 - 2
Display: times of wrong password
0 to 9999
Password input settings