5-8
5-3-2. Display of write protect level
Protect level
The write protect levels and their corresponding settings and operating condition are shown
below.
Write
protect
level
SW1
SW2
LSC (Key operation)
Communication
O
PER
AT
O
R'S
M
ODE
EN
GINEERIN
G
M
ODE
MAINTEN
AN
CE
M
ODE
O
PER
AT
O
R'S
M
ODE
EN
GINEERIN
G
M
ODE
MAINTEN
AN
CE
M
ODE
0
OFF
OFF
R/W
ENABLE
R/W
ENABLE
R/W
ENABLE
R/W
ENABLE
R/W
ENABLE
R/W
ENABLE
1
ON
OFF
R/W
ENABLE
R/W
ENABLE
R/W
ENABLE
R
ONLY
R
ONLY
R
ONLY
2
OFF
ON
R/W
ENABLE
R
ONLY
R/W
ENABLE
R
ONLY
R
ONLY
R
ONLY
3
ON
ON
R
ONLY
R
ONLY
R/W
ENABLE
R
ONLY
R
ONLY
R
ONLY
R/W:
Read and write (Reads and writes set values.)
R:
Read
W: Write
ENABLE: Enabled
Disable: Disabled
ONLY: Only the indicated operation is enabled.
Note) Be sure to turn off the power supply before changing the write protect level dip switch
settings.