7-33
7-3-2. Output check
Analog output check with MGZ calibrator
This function is used for the loop check using MGZ calibrator. 0%, or 25% to 100% of setting
range can be selected for the analog output check with MGZ calibrator.
To output fixed value of analog current by using MGZ calibrator, proceed as follows.
1. From online menu,
Select:
1. Device setup
2. Diag/Service
2. Loop test
1. Loop check mode
Fig. 7-73. is then displayed.
OK
EXIT
ENTER
ESC
ABORT
DEL
SAVE HOME
HELP
MAGNEW2W: ** ******
Choose output check
STOUT
1 Start
2 Exit
Fig. 7-73.
2. Once the display as shown Fig. 7-73.
appears, make sure that the loop is
removed from the automatic control.
Then press “OK” to execute the output
check with MGZ calibrator. Then Fig.
7-74. is displayed.
Move the arrow key up or down and select
“1 Start” to execute the loop check.
OK
EXIT
ENTER
ESC
ABORT
DEL
SAVE HOME
HELP
MAGNEW2W: ** ******
Set another value
Close
Close
Open
Fig. 7-74.
3. During the loop check, Fig. 7-75. is displayed. If the loop check is finished, move the
arrow key up or down and select “1 End” to select other analog output value for the loop
check. If you finish the loop check, move the arrow key up or down and select “2 Abort”
to abort. Then Fig. 7-76. is displayed.
OK
EXIT
ENTER
ESC
ABORT
DEL
SAVE HOME
HELP
MAGNEW2W: ** ******
Device Status
1 Status group 1
2 Status group 2
3 Status group 3
Fig. 7-75.
Fig. 7-76.
4. Once the display as shown Fig. 7-76. appears, press “OK” to abort. Then Fig. 7-77. is
displayed. Press “OK” and then the screen returns to the loop test menu as shown in Fig.
7-78.
OK
EXIT
ENTER
ESC
ABORT
DEL
SAVE HOME
HELP
MAGNEW2W: ** ******
Tag
*** *****
* *** ****
Fig. 7-77.
Fig. 7-78.
Summary of Contents for MagneW Two-wire PLUS+ MTG15A
Page 8: ...vi...
Page 22: ...1 14...
Page 56: ...2 34...
Page 60: ...3 4 Fig 3 2...
Page 66: ...3 10...
Page 70: ...4 4...
Page 144: ...5 74...
Page 226: ...6 82...
Page 268: ...7 42...
Page 274: ...8 6...
Page 275: ......
Page 278: ......
Page 280: ......