5-6-13. Selecting failsafe mode for analog outputs
This function is used to determine the analog output direction when the flowmeter detects a
critical status condition.
CAUTION
The failsafe mode is very important for the overall safety of the control process. Choose the
failsafe direction carefully, as equipment damage can result from a wrong choice.
Setting range:
LOW Analog output is driven to low scale (TYP 3.7 mA)
HIGH Analog output is driven to high scale (TYP 21.8 mA)
HOLD Analog output is held at its last good value.
Default:
LOW
Set failsafe mode for analog output in accordance with the following procedure:
Step
Procedure
Screen
1
Enter ENGINEERING MODE in accordance with the
entry into ENGINEERING MODE (see section 5-5-
10. on page 5-33). Then press the
or
key to
display the screen at right.
12.3 %
# ERROR OUT MODE
I.OUT
LOW
2
Press the
key.
12.3 %
# ERROR OUT MODE
I.OUT
LOW
3
Using the
or
key, determine the failsafe mode for
analog output.
12.3 %
# ERROR OUT MODE
I.OUT
HIGH
4
Press the
key to move the cursor to the position
under #.
Press the MODE key to return to the
MEASUREMENT MODE and to save data.
12.3 %
# ERROR OUT MODE
I.OUT
HIGH
CAUTION
You have only ten minutes to return to MEASURING MODE to save the new value before
the system resets it to the previously saved value.
Summary of Contents for MagneW Two-wire PLUS+ MTG15A
Page 8: ...vi...
Page 22: ...1 14...
Page 56: ...2 34...
Page 60: ...3 4 Fig 3 2...
Page 66: ...3 10...
Page 70: ...4 4...
Page 144: ...5 74...
Page 226: ...6 82...
Page 268: ...7 42...
Page 274: ...8 6...
Page 275: ......
Page 278: ......
Page 280: ......