6-76
Setting pulse width [PULSE CONFIGURE] function
Use the following procedure to set the pulse width. Available setting range of pulse width is
DUTY rate < 70%
Step
Key
Procedure
SFC screen
1
CLR
( No )
Confirm that the SFC is set to “READY”.
If it is not, press the
CLR
( No )
key to set it
to “READY”.
SFCM00006009D
2
B
CONF
H
NEXT
or
L
PREV
Press the
B
CONF
key to access the
CONFIG functions. Press the
H
NEXT
key or
L
PREV
key to display the screen
as shown on the right.
SFCM00006136D
SFCM00006020D
3
ENTER
( Yes )
NON-VOL
H
NEXT
or
L
PREV
Press the
ENTER
( Yes )
NON-VOL
key to access the
TOTALIZER functions. Press the
H
NEXT
key or
L
PREV
key to display
the screen as shown on the right.
SFCM00006142D
4
ENTER
( Yes )
NON-VOL
H
NEXT
or
L
PREV
Press the
ENTER
( Yes )
NON-VOL
key to enter into
PULSE setting function and press the
H
NEXT
key or
L
PREV
key to display
the screen as shown on the right.
Displays the actual pulse width.
SFCM00006150D