7-34
Analog output check
To output fixed value of analog current, proceed as follows:
1. From online menu,
Select:
1. Device setup
2. Diag/Service
2. Loop test
2. Out put check AO
Fig. 7-79. will then be displayed.
If the control system is not affected by the
forcible change of the current signal, press
F4 (OK). By pressing F3 (ABORT), the
procedure is canceled.
Fig. 7-79.
2. Fig. 7-80. will then appear. Choose
START to start fixed value of analog
current output, and then press F4
(ENTER)
Fig. 7-80.
3. Note of caution will appear as shown in
Fig. 7-81. To proceed, press F4 (OK).
Fig. 7-81.
4. Use the numeric keys to enter a fixed
value to be output in the value input
display. Setting range is duty ratio of 0%
to +100%. When value is entered, press F4
(ENTER). Analog current corresponding
to its output will be output. Press F3
(ABORT) to return to the previous menu.
Fig. 7-82.