6-37
Printing internal data: PRINT key
Used when
Configuration printout (data printout) is used to print out internal data of the converter such
as a damping time constant, low flow cutoff, etc.
Procedure
Use the following procedure to carry out configuration printout.
Step
Key
Procedure
SFC screen
1
Start communication between the SFC
and converter. For a detailed procedure,
see “Starting communication: ID/DE
2
CLR
( No )
Make sure that the SFC is set to
“READY”.
If it is not, press the
CLR
( No )
key to set it
to “READY”.
SFCM00006009D
3
SHIFT
Press the
SHIFT
key.
SFCM00006002D
4
P
9
Press the
P
9
key.
Result:
Configuration printout starts.
SFCM00006015D
SFCM00006016D
5
CLR
( No )
When printing is completed, press the
CLR
( No )
key to return step 2.