5-29
Selecting the Electrode Status Output Mode
Setting the output mode when the Electrode Status Diagnostic function detects the empty or
scale on electrode status.
There are the following three electrode status output modes.
OFF
ZERO
HOLD
Default setting: OFF
Detailes of the “Electrode Status Output mode”
Output / Display
Parameter selection in the “Electrode status output mode”
OFF
ZERO
HOLD
Analog 4 - 20 mA
output
Output values as the
meter measures.
Analog output is fixed
to 0% (4 mA).
Analog output is held
at its last good value.
Pulse output
Output values as the
meter measures.
Pulse output is fixed
to 0 (does not generate
pulses).
Pulse output is held at
its present state.
Display
Display the value as it
measures.
Flashes the message
0% and “Empty or
scale on electrode”
alternately (when %
flow rate is specified
for the main display).
Flashes the message
0.000 RATE and
“Empty or scale on
electrode” alternately
(when actual flow rate
is specified for the
main display). Flashes
the message
XXXXXXXX
(totalized value at
setup) and “Empty or
scale on electrode”
alternately (when
totalized value is
specified for the main
display).
Flashes the values at
its last good values
and a message of
“Empty or scale on
electrode” alternately.
Summary of Contents for MagneW Two-wire PLUS+ MTG15A
Page 8: ...vi...
Page 22: ...1 14...
Page 56: ...2 34...
Page 60: ...3 4 Fig 3 2...
Page 66: ...3 10...
Page 70: ...4 4...
Page 144: ...5 74...
Page 226: ...6 82...
Page 268: ...7 42...
Page 274: ...8 6...
Page 275: ......
Page 278: ......
Page 280: ......