User Manual
KDC Series II DC Power Supplies
111
Rev
Section
Test Requirement
Exception
Comments
270VDC
E
HDC103
Voltage distortion
spectrum
50kHz
Required frequency range exceeds
KDC capability.
Requires additional
equipment
D
HDC103
Voltage distortion
spectrum
20kHz
Required frequency range exceeds
KDC capability.
Requires additional
equipment
D, E
HDC104
Ripple Test
16.8kHz
Required ripple frequency range
exceeds KDC capability.
–704
option applies 400 Hz ripple only.
Requires additional
equipment
D
HDC105
Normal Operation,
Voltage Transients
Output voltage change may be
longer than 1 msec.
Requires KDC600 model to
support 475Vdc test level.
E
HDC105
Normal Operation,
Voltage Transients
Output voltage change may be
longer than 1 msec.
Requires KDC400 model to
support 330Vdc test level.
D, E
HDC201
Power Interrupt,
Voltage change
< 250 usec
Output voltage transient time
exceeds requirement.
Hardware limit
D
HDC302
Abnormal Operation,
Voltage Transients
Output voltage change may be
longer than 1 msec.
Requires KDC600 model to
support 475Vdc test level.
E
HDC302
Abnormal Operation,
Voltage Transients
Output voltage change may be
longer than 1 msec.
Requires KDC400 model to
support 350Vdc test level.
D, E
HDC501
Starting Voltage
Transient
Output voltage change may be
longer than 1 msec.
Table 11-1: KDC restrictions -704 option
Summary of Contents for KDC 100-100
Page 2: ......
Page 10: ......
Page 26: ...User Manual 16 KDC Series II DC Power Supplies Figure 3 1 Location of rear panel connectors ...
Page 33: ...User Manual KDC Series II DC Power Supplies 23 Figure 4 3 Front panel layout ...
Page 82: ......
Page 83: ...User Manual KDC Series II DC Power Supplies 73 Figure 6 1 DC Power Supply Block Diagram ...
Page 111: ...User Manual KDC Series II DC Power Supplies 101 Figure 8 2 Replaceable Fuse Locations ...