User Manual
64
KDC Series II DC Power Supplies
5.2.1.3 Master unit controller configuration
The master unit‟s controller must be configured as a Master. Unless the unit was originally
shipped as an auxiliary (-AUX on model tag), it should be set to master already. If not, install
jumper W17 and remove jumper W18.
If the total system power is from 15 KW to 45 KW install jumper W13 on the Master Controller
board, 5005-721. In addition install W14 if the power is from 45 to 60 KW. Settings for W13 and
W14 on the auxiliary (-AUX) uni
t‟s controller(s) are not relevant.
KDC II Master or Auxiliary Controller jumper settings
Available configuration settings are shown in the table below.
Configuration Option
W17
W18
Master
1
0
Auxiliary (-AUX)
0
1
Table 5-1: Master or Auxiliary Controller Configuration Jumper Settings
Relevant power level configuration settings for the MASTER controller only are shown in the table
below. The auxiliary units (-AUX) jumper settings for W13 and W14 are not relevant.
Check these settings if the system was not configured for parallel operation at this power level at
the factory.
Configuration Option
W13
W14
Master, 5 KW, 10 KW
0
0
Master, 15 KW
1
0
Master / AUX 15 to 45 KW
1
0
Master / AUX 45 to 60 KW
1
1
Table 5-2: Master Configuration Jumper Settings
Note:
If the system was not configured for parallel operation at this power level at
the factory or has been reconfigured from its original shipped
configuration, it will be necessary to check the current programming
calibration.
This can be accomplished in one of two ways:
1. Check and as needed recalibrate the full-scale output current programming, or
2. Load the calibration coefficient for the selected mode of operation in the Calibration
screen.
Since the number of DC amplifiers is different when the master unit is used stand alone as
opposed to the Master of a multi-box system, the current loop gain will be different and thus the
current calibration will shift. To correct for this, the correct calibration coefficient must be entered.
If the same unit is used often as either a stand-alone master unit or a multi-box master unit, it is
advisable to note down the full-scale current calibration coefficients for each configuration.
See chapter 7.4 for calibration details.
Summary of Contents for KDC 100-100
Page 2: ......
Page 10: ......
Page 26: ...User Manual 16 KDC Series II DC Power Supplies Figure 3 1 Location of rear panel connectors ...
Page 33: ...User Manual KDC Series II DC Power Supplies 23 Figure 4 3 Front panel layout ...
Page 82: ......
Page 83: ...User Manual KDC Series II DC Power Supplies 73 Figure 6 1 DC Power Supply Block Diagram ...
Page 111: ...User Manual KDC Series II DC Power Supplies 101 Figure 8 2 Replaceable Fuse Locations ...