2. External Voltage Programming using a resistor. The resistance coefficient for remote voltage
programming is 5k ohms/100% of rated output voltage with respect to the (ISO VP/IP RTN),
pin 6. The programming current from pin 13 (VP RES) is 1 milliamp through a 5 V DC supply.
This yields a coefficient of 1.0% of rated output current for each 50 ohms. If multiple switches
or relays are used to program different levels, make-before-break contacts are
recommended. See Figure 5-2
for connection requirements.
From the CONTROL menu, set the VOLTAGE REF to EXTRES
1
8
9
15
ANALOG I/O
VP/IP RTN 6
13 VP RES
0 - 5 KOHM
PROGRAM
VPROG 5V 3
Figure 5-2: Remove Voltage Programming Using Resistance
3. External Voltage Programming using an external current source. This is similar to the use of
a voltage source except the available current source is converted to a voltage source by using
an external resistor. If the current source is fixed, a variable resistor will result in a voltage
input to the RPV input proportional to the resistor setting. See Figure 5-2
for connection
requirements.
From the CONTROL menu, set the VOLTAGE REF to EXT5V.
1
8
9
15
ANALOG I/O
VPROG 5V 3
14 ISO COM
CURRENT
SOURCE
R
Figure 5-3: Remote Voltage Programming Using a Current Source
Summary of Contents for KDC 100-100
Page 2: ......
Page 10: ......
Page 26: ...User Manual 16 KDC Series II DC Power Supplies Figure 3 1 Location of rear panel connectors ...
Page 33: ...User Manual KDC Series II DC Power Supplies 23 Figure 4 3 Front panel layout ...
Page 82: ......
Page 83: ...User Manual KDC Series II DC Power Supplies 73 Figure 6 1 DC Power Supply Block Diagram ...
Page 111: ...User Manual KDC Series II DC Power Supplies 101 Figure 8 2 Replaceable Fuse Locations ...