background image

VACON NX QUICK HELP 

 
Start-up wizard 

 
The Start Up Wizard is activated when the power to the drive is turned on for the first time, or if the 
Start Up Wizard is activated from the System menu (P6.5.3) AND the power is turned OFF and back 
ON. 

The Start-up Wizard is a feature on the control keypad to facilitate the commissioning of the fre-
quency converter. If selected active (default), the Start-up Wizard prompts the operator for the lan-
guage and application of his/her choice plus for the values for a set of parameters common to all 
applications as well as for a set of application-dependent parameters. 

Always accept the value with the 

Enter button

, scroll options or change values with the 

Browser 

buttons

 (up and down arrows). More information on the use of the control panel in Chapter 7 of the 

User's Manual.

enter

Basic application:

I/O reference (P2.14)

Standard application:

I/O reference (P2.1.11)

Local/Remote control
application:

I/O reference A (P2.1.11)
I/O reference B (P2.1.12)

Multi-step speed
application:

I/O reference (P2.1.11)

PID control application:

Act value 1 selection (P2.2.9)
PID controller ref (P2.1.11)

Multi-purpose control
application:

I/O reference  (P2.1.11)

Pump and fan control
application:

Act value 1 select (P2.2.1.9)
PID controller ref (P2.1.11)
No. of aux pumps (P2.9.1)

enter

enter

enter

enter

Nine parameter settings
are prompted for each
application:

Min Frequency

0.00 Hz

Additional parameter settings are prompted
depending on the selected application.

Repeat setup?

<No

  Yes>

Application

Standard

Setup starts

Press enter

Language

English

Startup wizard

Press enter