background image

 

NOTE! There are some special functions that can be performed when in the 

M3

 menu: 

Select the keypad as the active control place by keeping the 

start

button pushed 

down for 3 seconds when the motor is running. The keypad will become the active 
control place and the current frequency reference and direction will be copied to the 
keypad. 

Select the keypad as the active control place by keeping the 

stop

 button pushed 

down for 3 seconds when the motor is stopped. The keypad will become the active 
control place and the current frequency reference and direction will be copied to the 
keypad. 
 
Copy the frequency reference set elsewhere (I/O, fieldbus) to the panel by keeping the 

enter

 button pushed down for 3 seconds. 

 

Note that if you are in any other than 

M3 menu these functions will not work. 

If you are in some other than 

M3 menu and try to start the motor by pressing the START button 

when the keypad is not selected as the active control place you will get an error message 

Keypad 

Control NOT ACTIVE. 

NOTE 2: 

By default, the motor can be stopped at all times by pushing the 

stop

 button 

regardless of the selected control place. This default setting can be inactivated by giving 
parameter 

Stop Button Activated 

(P3.4 or P3.6) (menu M3) the value 0. With this value 

given to the parameter, pushing the STOP button stops the motor only when the keypad 
has been selected as the active control place. 

Reviews: