Asterion DC Multioutput ASA Series Operational Manual
M330516-01
2-4
3. Adjust the location of the mounting brackets as required for the rack cabinet
vertical rails utilized.
4. Mount the cabinet sections of the slides, item #1C, (with brackets already
installed) into the cabinet using appropriate hardware (e.g., the screws and
nuts supplied, item #6 and item#7, or user-supplied bar-nuts, cage-nuts, clip-
nuts), while ensuring that they are level, front to back and left to right, on the
cabinet rails.
5. Insert adjustable side sections, item #1B (supplied as part of item #1), into
cabinet slide sections, item #1C. Insert power supply chassis with installed
slide sections, item #1A, into the adjustable slide sections, item #1B.
Figure 2-1:
Rack mounting, 1U Multi output Asterion DC Series Model
2.5
Chassis Removal from Rack
The slides have a front disconnect feature and lock at full extension. To disconnect
and remove the chassis from the rack, depress the flat steel spring (located on the
slides) inward, and pull the chassis forward. To return the chassis back into the rack