Asterion DC Multioutput ASA Series Operational Manual
M330516-01
1-5
1.2
Specifications
The following sections provide electrical, environmental, and physical specifications
for the Asterion DC Multioutput Series power supplies.
Unless otherwise noted, the specifications are valid under the following conditions:
a. Ambient temperature of 25
5
C, after a 30-minute warm-up, and at fixed AC
input line and load.
b. DC output into a resistive load.
c. Specifications values are valid from 5% of the full-scale value.
d. Stability is over an 8-hour period after a 30-minute warm up.
e. If remote sense is used then the output voltage accuracy, regulation and
stability specifications are valid at the point where the remote sense leads are
connected.
1.2.1
Output Power
Model
Per channel Power
Total power (3
– Channels)
ASA Series
600 W
1800 W
Table 1-2: Output Power for ASA Series
1.2.2
ASA Series Output Voltage and Current Ratings
Voltage
Current
60 V
42 A
80 V
22 A
200 V
17 A
400 V
6 A
Table 1-3: Channel ratings for Asterion DC Multioutput ASA Model Series
Asterion DC Multioutput ASA Series, provides extended wide range output voltage
and Current channels as provided in Table 1-3 and the power is rated at 600 W. The
output current versus output voltage follows a constant-power curve to provide users
a wider current and voltage operating range in a single power supply. The Extended
Wide Range Voltage Vs Current Characteristics of the different ratings are shown in
the Figure 1-3. The three channels would cover a wide range of voltage and current
requirements for the customer.