Asterion DC Multioutput ASA Series Operational Manual
M330516-01
2-2
8. Crimp pins for Analog programming Mating Connector, Refer to Item 8 in Table
Item
No
Part
number
Description
Qty Manufacturer
Manufacturer Part number
1
893-006-06
TERM BLK,6P,41A,1KV, PLG,7.62MM
3
(1)
Phoenix
1777875
2
M550008-01
MANUAL, SORENSEN, CD ROM
1
Ametek
M550008-01
3
893-004-41
TERM BLK,4P,41A,1KV, PLG,7.62MM
1
Phoenix
1709173
4
9330722-01R
COVER, SFTY O/P, MLT O/P, DC -AST
1
Ametek
9330722-01R
5
9330655-01R
COVER, DC INPUT, 1U
1
Ametek
9330722-01R
6
MN-M04K-07
NUT M4X0.7 KEPS STEEL ZN PLATE
6
Any
M4 -0.7 KEPS Zinc Plated Steel
7
856-144-22
CONN, 8P, HOUSING,1R, 3MM, CRIMP
3
(2)
TE Connectivity
1445022-8
8
856-794-10
CONTACT, SKT, 20-24AWG, CRIMP, TIN
24
(3)
TE Connectivity
794610-1
(1)
Qty would be 2 Nos for the two-channel power supply; Terminal block is assembled with a label indicating the pin details.
(2)
Qty would be 2 Nos for the two-channel power supply, Item No 7 is supplied when only Isolated Analog Programming option is
Ordered
(3)
Qty would be 16 Nos for the two-channel power supply, Item No 7 is supplied when only Isolated Analog Programming option is
Ordered
Table 2-1: Ship Kit Details
Note:
If any of these parts are missing, contact AMETEK Customer Service Department at
858-458-0223 (local) or 1-800-733-5427 (toll free).
Optional accessories:
1. 5330201-01R: Rackmount slide kit; includes two slides with rack adapter brackets
and mounting hardware.
2.3
Mechanical Installation
The Asterion DC Multioutput Series power source is designed for rackmount
applications, there is an option for a rack mounted slide. Rack mounting requires
installing the flange brackets with handles to the side of the chassis: using M4-0.7 x 6
mm Philips flat-head screws to mount the brackets to the chassis, and # 8-32 Philips
flat-head screws to mount the handles to the brackets.
The unit is forced air cooled with internal fans drawing air in from the front and sides
and exhausting at the rear. The front and rear of the unit must be kept clear of
obstruction and clearance must be maintained to allow unimpeded airflow. The same
consideration given to the side grilles will minimize internal temperature rise. Special
consideration must be made to overall air flow characteristics, and the resultant
internal heat rise, when a source is installed inside enclosed cabinets to avoid
excessive heating and over-temperature problems. The temperature of the ambient
air at the air intake should not exceed 50°C.