Asterion DC Multioutput ASA Series Operational Manual
M330516-01
2-3
WARNING!
This unit is intended for installation in a protected environment. Exposure to
conductive contaminants or corrosive compounds/gases that could be ingested into
the chassis could result in internal damage. Install the power source in a
temperature and humidity controlled indoor area.
CAUTION!
The power source should be provided with proper ventilation. The front and rear of
the unit must be free of obstructions. To ensure proper airflow, a minimum 2"
clearance from the rear air outlet is required.
CAUTION!
No user serviceable parts are inside; service is only to be performed by qualified
personnel.
2.4
Rack Mounting
The Asterion DC Multioutput Series power source is designed for mounting in a
standard 19-inch equipment rack that is compliant to ANSI/EIA-310-D. If other
instrumentation is mounted in the rack adjacent to the unit, there is no need for
additional clearance above or below the source. It should be supported in the rack
using appropriate L-brackets or rackmount slides. Refer to Figure 2-1 for typical
rackmount installation. The rack mounting slide kit, part number
5330201-01R
consists
of the following items:
Part Number
Description
MFG
Item #
Qty
105-510-24
RACK SLIDES,FRICTION,24 IN,SS
JONATHAN 510QD-24
1
2
9330325-01R
BRKT, RACKSLIDE -DYN
AMETEK
2
4
110-800-06
SCREW,8-32 X .375,PFH100,LK,SS
ANY
4
14
112EN04-01
NUT,8-32,W/CONE WASHER,KEP,CS
ANY
5
8
110GS04-08
SCREW,10-32 X .500,SEMS,PPH,CS
ANY
6
12
112Gl04-01
NUT, 10-32, ZINC PL
ANY
7
12
Note: Item #1 consists of three parts (item #1A, item #1B and item #1C) as shown in
Figure 2-1.
Install the rackmount kit as follows:
1. Install the slide sections item #1 (supplied as part of item #1) on both sides of
the power supply chassis with screws, item #4 (three on each side).
2. Install the brackets, item #2, , to the cabinet sections of the slides, item #1C
(supplied as part of item #1) , with screws, item #4, and nuts, item #5 (four on
each side).